2 Introduction: Parameterising the inverter
2.4 Device access protection
48
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Activate device personalisation
The device personalisation is activated by setting a binding ID.
How to set the binding ID:
1. Enter the desired binding ID in C00505/2
.
The binding ID must have a length of 4 ... 16 characters.
The binding ID may consist of any character. However, this is not sensible.
Recommended characters are: lower case letters (a - z), upper case letters (A - Z) and
digits (0 - 9).
2. Execute "Set binding ID" device command C00002/29
= "1: On / start"
After successful execution, status ON is displayed in C00505/2
.
Deactivate device personalisation/change binding ID
The device personalisation is simply deactivated by deleting the set binding ID. If you want to
change the set binding ID, first delete the set binding ID as well. Then set the new binding ID.
How to delete the binding ID:
1. Enter the set binding ID in C00505/2
.
If inverter and memory module do not have the same binding ID, enter the binding ID of
the memory module to delete the binding ID of both components.
2. Execute "Delete binding ID" device command C00002/30
= "1: On / start"
After a successful deletion, status OFF is displayed in C00505/2
.
Device commands
Before
the following device commands are executed, enter the corresponding binding ID in C00505/2.
C00002/29
Set binding ID
Activate device personalisation
0: Off / ready
C00002/30
Delete binding ID
Deactivate device personalisation/change binding ID
0: Off / ready
Status displays
C00003 Status of the last device command -
C00507/1 Password protection - all communication channels
Bit coded display of the active protective functions:
-
Bit 0 Only access to user menu
Bit 1 Parameter write protection
Bit 2 Parameter read protection
Bit 3 ... 14 Reserved
Bit 16 Memory module binding on
Parameters Info Lenze setting
Greyed out = display parameter