Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 763
11 System bus "CAN on board"
11.11 CANopen objects implemented | I-1201
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1201
Identifiers for SDO server channel 2.
• The SDO server parameter is only valid, if bit 31 is set to "0" for both transmission directions
(subindex 1 and 2).
• In the Lenze setting, the SDO server channels 2 are deactivated (bit 31 = "1").
• The identifier can only be changed if the SDO is invalid (bit 31 = "1").
[11-6] Data telegram assignment
How to change the identifier:
1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").
Index:
I-1201
Name:
SDO2 server parameter
Subindex Default setting Setting range (min. value | unit | max. value) Access Data type
0: Highest subindex supported 3 - (read access only) ro U8
1: COB-ID client -> server (rx) 0x80000000 0 4294967295 rw U32
2: COB-ID server -> client (tx) 0x80000000 0 4294967295 rw U32
Subindex Meaning
1 Specification of receive identifier
2 Specification of send identifier
8th byte 7th byte 6. byte 5th byte
Data 4 Data 3 Data 2 Data 1
Bit 31 Bit 30 Bit 29 ... bit 11 Bit 10 ... bit 0
0/1 0 Extended identifier* 11-bit identifier
* The extended identifier is not supported. Bit11...bit29 must be set to "0".
Bit setting
Bit 31 0 SDO is valid.
1 SDO is invalid.