15 Parameter reference
15.2 Parameter list
810
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00002/1 0: Off / ready Load Lenze setting
• All parameters are reset to the Lenze setting.
• Only possible when the controller is inhibited.
Load Lenze setting
C00002/2 0: Off / ready Reserved
C00002/3 0: Off / ready Reserved
C00002/4 0: Off / ready Reserved
C00002/5 0: Off / ready Reserved
C00002/6 0: Off / ready Load all parameter sets
• All parameter sets are loaded by the memory module.
• Only possible when the controller is inhibited.
Load all parameter sets
C00002/7 0: Off / ready Reserved
C00002/8 0: Off / ready Reserved
C00002/9 0: Off / ready Reserved
C00002/10 0: Off / ready Reserved
C00002/11 0: Off / ready Save all parameter sets
• All parameter sets are saved to the memory module
safe against mains failure.
Save all parameter sets
C00002/12 0: Off / ready Reserved
C00002/13 0: Off / ready Reserved
C00002/14 0: Off / ready Reserved
C00002/15 0: Off / ready Reserved
C00002/16 1: On / start Enable inverter
1 ≡ Enable inverter
0 ≡ Inhibit inverter
Enable/inhibit inverter
C00002/17 0: Off / ready Activate quick stop
1 ≡ Activate quick stop
0 ≡ Deactivate quick stop
Activate/deactivate quick stop
C00002/18 0: Off / ready Reserved
C00002/19 0: Off / ready Reset error
• After the reset (acknowledgement) of the current
error, further errors may be pending which must also
be reset.
• The status determining error is displayed in C00168
.
• The current error is displayed in C00170
.
Error messages of the operating system
C00002/20 0: Off / ready Reserved
C00002/21 0: Off / ready Delete logbook
• All entries in the logbook of the inverter are deleted.
• In the logbook, information on the error history is
saved.
Logbook
C00002/22 0: Off / ready Reserved
Parameter | Name:
C00002 | Device command
Data type: UNSIGNED_8
Index: 24573
d
= 5FFD
h