C00221
C00222
C00223
C00224
C00225
Parameter | Name:
C00221 | L_NSet_1: Deceleration time - add. setpoint
Data type: UNSIGNED_32
Index: 24354
d
= 5F22
h
The L_NSet_1 FB: Deceleration time for the additional setpoint nNAdd_a
Setting range (min. value | unit | max. value) Lenze setting
0.000 s 999.999 0.000 s
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000
Parameter | Name:
C00222 | L_PCTRL_1: Vp
Data type: INTEGER_16
Index: 24353
d
= 5F21
h
The L_PCTRL_1 FB: Gain factor Vp for the PID process controller
Setting range (min. value | unit | max. value) Lenze setting
0.1 500.0 1.0
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 10
Parameter | Name:
C00223 | L_PCTRL_1: Tn
Data type: UNSIGNED_16
Index: 24352
d
= 5F20
h
The L_PCTRL_1 FB: Reset time Tn for the PID process controller
Setting range (min. value | unit | max. value) Lenze setting
20 ms 6000 400 ms
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00224 | L_PCTRL_1: Kd
Data type: UNSIGNED_16
Index: 24351
d
= 5F1F
h
The L_PCTRL_1 FB: Derivative-action coefficient Kd for the PID process controller
Setting range (min. value | unit | max. value) Lenze setting
0.0 5.0 0.0
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 10
Parameter | Name:
C00225 | L_PCTRL_1: MaxLimit
Data type: INTEGER_16
Index: 24350
d
= 5F1E
h
The L_PCTRL_1 FB: Maximum output value of the PID process controller
Setting range (min. value | unit | max. value) Lenze setting
-199.99 % 199.99 199.99 %
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100