2.1 General Specifications
The following table shows the general specification of XGB series.
No. Items Specifications Related standards
1
Ambient
temperature
0 ~ 55 °C
2
Storage
temperature
25 ~ +70 °C
3
Ambient
humidity
5 ~ 95%RH (Non-condensing)
4
Storage
humidity
5 ~ 95%RH (Non-condensing)
Occasional vibration -
Frequency Acceleration Amplitude
How many
times
10 f < 57Hz
0.075mm
57 f 150Hz 9.8m/s
2
(1G)
Continuous vibration
Frequency Acceleration Amplitude
10 f < 57Hz
0.035mm
5
Vibration
resistance
57 f 150Hz
4.9m/s
2
(0.5G)
10 times each
directions
(X, Y and Z)
IEC61131-2
6
Shock
resistance
Peak acceleration: 147 m/s
2
(15G)
Duration: 11ms
Half-sine, 3 times each direction per each axis
IEC61131-2
Square wave
Impulse noise
±1,500 V
LSIS standard
Electrostatic
discharge
4kV (Contact discharge)
IEC61131-2
IEC61000-1-2
Radiated
electromagnetic
field noise
80 ~ 1,000 MHz, 10V/m
IEC61131-2,
IEC61000-1-3
Segm
ent
Power supply
module
Digital/analog input/output
communication interface
7
Noise
resistance
Fast
transient/bust
noise
Voltage 2kV 1kV
IEC61131-2
IEC61000-1-4
8 Environment Free from corrosive gasses and excessive dust
9 Altitude Up to 2,000 ms
10
Pollution
degree
Less than equal to 2
11 Cooling Air-cooling
N0ote
1) IEC (International Electrotechnical Commission):
An international nongovernmental organization which promotes internationally cooperated standardization in
electric/electronic field, publishes international standards and manages applicable estimation system related with.
2) Pollution degree:
An index indicating pollution degree of the operating environment which decides insulation performance of the devices. For
instance, Pollution degree 2 indicates the state generally that only non-conductive pollution occurs. However, this state contains
temporary conduction due to dew produced.