Chapter 4 Positioning Parameter & Operation Data
4-19
4.5 I/O
Signal Parameter
Here describes using input/output signal parameter in positioning module.
Input/output signal parameter use to decide act level of input signal.
4.5.1 I/O Signal Parameter
Input/output signal parameter
configuration
Setting range
Upper limit signal
Lower limit signal
DOG signal
Home signal
In position signal
0 : A contact 1 : B contact
4.5.2 Setting of I/O Signal Parameter
In case of setting the input signal by A contact, it acts when external is ON and in case of setting by B contact, it acts when
external signal is OFF
(1) If setting the high limit signal of input signal parameter by A contact and the low limit signal by B contact, the high limit is
detected when external high limit signal is ON while the low limit is detected when external low signal is OFF.
(2)
If setting the origin signal of input signal parameter by A contact, the origin is detected when external origin signal is ‘Rising
edge’, while if setting by B contact, the origin is detected when external origin signal is ‘Falling edge’.