10.28
SEL-311C Relay Instruction Manual Date Code 20060320
Serial Port Communications and Commands
Command Explanations
(Continued from previous page)
Press RETURN to continue
DP7 =0
DP8 =0
DP9 =0
DP10 =0
DP11 =0
DP12 =0
DP13 =0
DP14 =0
DP15 =0
DP16 =0
SS1 =0
SS2 =0
SS3 =0
SS4 =0
SS5 =0
SS6 =0
ER =/M2P + /Z2G + /51G + /51Q + /50P1 + /LOP
FAULT =51G + 51Q + M2P + Z2G
BSYNCH=0
CLMON =0
Press RETURN to continue
E32IV =1
=>
=>SHO G <Enter>
Global Settings:
TGR = 180.00 NFREQ = 60 PHROT = ABC
DATE_F= MDY FP_TO = 15.00 SCROLD= 5
LER = 15 PRE = 4 DCLOP = OFF DCHIP = OFF
IN101D= 0.00 IN102D= 0.00 IN103D= 0.00 IN104D= 0.00
IN105D= 0.00 IN106D= 0.00
IN201D= 0.00 IN202D= 0.00 IN203D= 0.00 IN204D= 0.00
IN205D= 0.00 IN206D= 0.00 IN207D= 0.00 IN208D= 0.00
EBMON = N
=>
=>SHO P <Enter>
Port F
PROTO = SEL
SPEED = 2400 BITS = 8 PARITY= N STOP = 1
T_OUT = 15 DTA = N AUTO = N RTSCTS= N FASTOP= N
=>
=>SHO R <Enter>
Sequential Events Recorder trigger lists:
SER1 =M1P,Z1G,M2P,Z2G,M3P,Z3G,51G,51Q,50P1
SER2 =IN101,IN102,OUT101,OUT102,OUT103,OUT104,LOP
SER3 =KEY,Z3RB,PTRX
=>