EasyManua.ls Logo

Schweitzer Engineering SEL-2032 - Page 300

Schweitzer Engineering SEL-2032
354 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.56
SEL-2032 Communications Processor Instruction Manual Date Code 20120126
Protocols
Distributed Network Protocol 3.0 (DNP3) LAN/WAN
Custom Data Mapping
NOTE: When DNPMAP = CUSTOM,
the SEL-2032 stores the most recent
value of all DNP points in its STATE
region. Like the User region, the
STATE region has one timestamp,
which indicates the time at which the
collective data was last updated.
However, the STATE region also has
an SER queue. It is the SER queue that
provides a per point history of time-
stamped changes within the region.
For this reason, you must set DNPMAP
= CUSTOM if you want to preserve
SER time stamps from an attached
IED all the way through to the DNP
Master.
By setting the DNPMAP parameter to CUSTOM, you have the ability to
specify the DNP3 data points available for up to 10 unique master sessions
using any of 5 distinct data maps. The most efficient way to set the DNP3 Map
mode and assign data maps to DNP3 masters is to use the SEL-5020 Settings
Assistant.
71 1:RB16/RB15 Pulse 1:SRB16 Pulse 1:SRB15 Pulse 1:SRB16 Pulse 1:SRB15 Pulse 1:SRB16 Pulse 1:SRB15
72 2:RB02/RB01 Pulse 2:SRB02 Pulse 2:SRB01 Pulse 2:SRB02 Pulse 2:SRB01 Pulse 2:SRB02 Pulse 2:SRB01
207 18:RB16/RB15 Pulse 18:SRB16 Pulse 18:SRB15 Pulse 18:SRB16 Pulse 18:SRB15 Pulse 18:SRB16 Pulse 18:SRB15
208 1:BR1 Pulse 1:CBR1 Pulse 1:SBR1 Pulse 1:SBR1 Pulse 1:CBR1 Pulse 1:SBR1 Pulse 1:CBR1
209 1:BR2 Pulse 1:CBR2 Pulse 1:SBR2 Pulse 1:SBR2 Pulse 1:CBR2 Pulse 1:SBR2 Pulse 1:CBR2
210 1:BR3 Pulse 1:CBR3 Pulse 1:SBR3 Pulse 1:SBR3 Pulse 1:CBR3 Pulse 1:SBR3 Pulse 1:CBR3
223 1:BR16 Pulse 1:CBR16 Pulse 1:SBR16 Pulse 1:SBR16 Pulse 1:CBR16 Pulse 1:SBR16 Pulse 1:CBR16
224 2:BR1 Pulse 2:CBR1 Pulse 2:SBR1 Pulse 2:SBR1 Pulse 2:CBR1 Pulse 2:SBR1 Pulse 2:CBR1
463 16:BR16 Pulse 16:CBR16 Pulse 16:SBR16 Pulse 16:SBR16 Pulse 16:CBR16 Pulse 16:SBR16 Pulse 16:CBR16
Table 9.30 SEL-2032 DNP3 Over Ethernet Object 12 Control Point Operation, DNPMAP = AUTO, DNPPAIR = Y
(Sheet 2 of 2)
DNP3
Indices
(Control
Pt. IDs)
Control Points
Trip / Close Pairs Code Selection Operation
Close (0x4X) Trip (0x8X) Latch On (3) Latch Off (4) Pulse On (1) Pulse Off (2)