Service Nur für den internen Gebrauch
A31003-H3590-S100-7-7620, 06/2012
12-62 HiPath 3000/5000 V9, Service documentation
service.fm
Guided Maintenance
Table 12-7 HiPath 3000 Class B Error Messages
No. HiPath 3000/
5000 Manager E:
Event Log Entry
Meaning Required Measures Note
Error Class 01 - General Messages
01-003 !System Restart Hard restart (reset)
of entire system
with current CDB.
None
01-010 !SNMP System
Restart
Hard restart of en-
tire system via SN-
MP.
None
01-014 local DB changes “On site” changes
to the database.
None
01-015 remote DB chang-
es
“Remote” changes
to the database.
None
01-016 !SNMP APSXF
result
APS transfer ac-
knowledgement
message via SN-
MP.
None
01-017 !SNMP authenti-
cation fail
Unauthorized ac-
cess attempt.
Check firewall settings in
HiPath 3000/5000 Manag-
er E (Network – Firewall).
01-018 !SNMP 80 % high
watermark of log-
file
Changes logged
internally in the
system: 80 % of
write capacity
used.
Read out data using Hi-
Path 3000/5000 Manager
E (Transfer – Security –
Protocol).
01-019 !Sensor Alarm Temperature in Hi-
Path 3500/HiPath
3300 19” housing
is too high.
Check the fan and air sup-
ply in the 19” housing.
Note the ambient tempera-
ture.
01-020 !CDR buffer limit
reached
Overflow in the
CDR buffer (CDR
information).
Check that the interfaces
(V.24, LAN), ports and the
connection are functioning
or read out call data.
01-021 !Authentication
Failure
Unauthorized ac-
cess attempt.
Check firewall settings in
HiPath 3000/5000 Manag-
er E (Network – Firewall).