Operator control panel OP2
Hardware - SIMADYN D 10-23
Edition 03.2001
10
No Text Description /cause/ corrective
action
Reference
(Chapter)
20
RAM-TEST
UNSUCCESSFUL,
REPLACE THE UNIT
OP2 has an electronics defect and
is not functioning: Self-test
message
2.1.2
21
FLASH TEST
UNSUCCESSFUL,
REPLACE THE UNIT
OP2 has an electronics defect and
is not functioning: Self-test
message
2.1.2
22
EPROM-INCORRECT
EPROM CHECKSUM,
REPLACE THE UNIT
OP2 has an electronics defect and
is not functioning: Self-test
message
2.1.2
34
INITIALIZATION
REQUESTED
OP2 waits for initialization data 2.3
35
EPROM SAVE
UNSUCCESSFUL
VAL/CHG/ save mode
unsuccessful in the EPROM
Check configuring.
1.2.3
37
PRINTER INTERFACE
OK
Self-test message
38
DEFECTIVEW PRINTER
INTERFACE
Self-test message
39
CALCULATING EPROM
CHECKSUM
Self-test message
40
RAM READ/WRITE TEST
Self-test message
41
FLASHRAM
READ/WRITE TEST
Self-test message
42
TEST OK
Self-test message