Basic information about the drive system
13.12 System rules, sampling times and DRIVE-CLiQ wiring
Drive functions
1006 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
The following applies when connecting Motor Modules in parallel:
A parallel connection is only permitted in the chassis format and only in the vector control
or V/f control mode.
A maximum of four Motor Modules are permitted in a parallel connection. All Motor
Modules connected in parallel must have the same output.
A drive object is created for a parallel connection.
Only one parallel connection exactly is permitted per Control Unit.
Line Modules
For the CU310-2 Control Unit the following applies:
Operating Line Modules is not permitted
For the CU320-2 Control Unit the following applies:
Only one drive object of the Smart Line Module (SLM), Basic Line Module (BLM) and
Active Line Module (ALM) types is permitted in each case.
Mixed operation of an Active Line Module with a Smart Line Module (SLM) or with a Basic
Line Module (BLM) is not permitted.
Mixed operation of a drive object of the Smart Line Module (SLM) type with a drive object
of the Basic Line Module (BLM) type is permitted.
An active Voltage Sensing Module (VSM) must be assigned to each active Active Line
Module (ALM) or Smart Line Module (SLM) of the chassis format. A violation of this rule
causes fault F05061 to be issued.
Two further Voltage Sensing Modules can be operated with the "network transformer"
function module for Active Line Modules (ALM).
The following applies to parallel connection of Line Modules:
Parallel connection is permitted for Infeed Modules in the chassis format and for Active
Line Modules (ALM) from the 120 kW performance class for the booksize format.
A maximum of four Infeed Modules are permitted within a parallel connection.
In booksize format, a maximum of two Active Line Modules (ALM) from the 120 kW
performance class are permitted within a parallel connection.
The operation of Infeed Modules with different performance values is not permitted within
a parallel connection.
An active Voltage Sensing Module (VSM) must be assigned to each Active Line Module
(ALM) in the parallel connection. A violation of this rule causes alarm F05061 to be
issued.
When using Smart Line Modules (SLM) an active Voltage Sensing Module (VSM) must
be assigned to at least one Smart Line Module (SLM) in the parallel connection. A
violation of this rule causes fault F05061 to be issued.

Table of Contents

Other manuals for Siemens SIROTEC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIROTEC and is the answer not in the manual?

Siemens SIROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIROTEC
CategoryDC Drives
LanguageEnglish

Related product manuals