Monitoring functions and protective functions
9.5 Thermal motor protection
Drive functions
664 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Sensor monitoring for wire breakage/short-circuit
● A sensor monitoring function for a short-circuit in the sensor cable is possible for a PTC
and a PT1000 or KTY84 sensor. Wire breakage monitoring is possible for a PT1000 or
KTY84 sensor:
If the temperature value lies outside the specified range of -140 °C ... +250 °C, then it is
probable that the sensor cable either has a broken wire or short-circuit. The alarm
A07015 "Drive: Motor temperature sensor alarm" is initiated. After the wait time in p0607
has expired, fault F07016 "Drive: Motor temperature sensor fault" is output.
● If an induction motor is connected, you can suppress fault F07016 by setting p0607 = 0.
The drive then continues to operate with the data calculated in the thermal 3-mass model.
● If the motor temperature sensor set in p0600 is not connected, alarm A07820
"Temperature sensor not connected" is triggered.
Function diagrams and parameters
Function diagrams (see SINAMICS S120/S150 List Manual)
8016
Signals and monitoring functions
- thermal monitoring motor, Mot_temp ZSW
8017
and monitoring functions - motor temperature model - 1 (I2t)
9576
Terminal Module 31 (TM31)
- Temperature evaluation
9605
Terminal Module 120 (TM120)
- Temperature evaluation, channels 0 and 1
9606
Terminal Module 120 (TM120)
- Temperature evaluation, channels 2 and 3
9625
Terminal Module 150 (TM150)
- Temperature evaluation structure (channel 0
9626
Terminal Module 150 (TM150)
- Temperature evaluation 1x2-, 3-, 4-wire
9627
Terminal Module 150 (TM150)
- Temperature evaluation 2x2-wire
Overview of important parameters (see SINAMICS S120/S150 List Manual)
r0034
r0035
r0068
CO: Absolute actual current value
p0318[0...n]
p0600[0...n]
temperature sensor for monitoring
p0601[0...n]
Motor temperature sensor type
p0602
Parallel connection power unit number temperature sensor