Communication
11.3 Communication via PROFINET IO
Drive functions
854 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
The following parameter assignments are possible:
Code for parameter assignment
PROFIdrive error classes 1
When establishing the communication between SINAMICS and a controller, the activated
diagnostics mode of this controller is first transferred to the drive. With activated diagnostics,
SINAMICS first transfers all pending messages to the controller. Similarly, all currently active
messages in the controller are deleted by SINAMICS when closing the communication
connection.
The message texts are described in detail in the SINAMICS S120/S150 List Manual, Chapter
"Explanations on the list of faults and alarms". A current list of the message texts can be
found in the "Message classes and coding of different diagnostics interfaces" table.
Support of I&M data sets 1...4
Identification & Maintenance (I&M)
I&M data sets contain information for a standardized and simplified identification and
maintenance of PROFIBUS/PROFINET devices. I&M data sets 1...4 contain plant-specific
information, such as the installation location and date. PROFINET supports I&M data sets
0...4.
I&M data sets 1...3 can be set with the SIMATIC Manager (STEP 7) and also with HW
Config (STEP 7).