Communication
11.3 Communication via PROFINET IO
Drive functions
852 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
PROFIenergy inhibit and pause time
Block PROFIenergy
If you set p5611.0 = 1, you inhibit the response of the inverter to PROFIenergy control
commands. In this case, the converter ignores the PROFIenergy control commands.
● Minimum pause time: p5602
– When the pause time, which is sent using command "Start_Pause", is equal to or
greater than the value in p5602[1], then the inverter goes into the energy-saving
mode.
– If the pause time is less than p5602[1], the inverter ignores the command.
● Maximum duration: p5606
Function diagrams and parameters
Function diagrams (see SINAMICS S120/S150 List Manual)
2381
- Control commands / query commands
2382
- States
2610
- Sequencer
Overview of important parameters (see SINAMICS S120/S150 List Manual)
r5600
p5602[0...1]
nation pause time, minimum
p5606[0...1]
Pe hibernation duration, maximum
p5611
-saving properties, general
r5613.0...1
-saving active/inactive