Basic functions
7.17 Runtime (operating hours counter)
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
365
Time stamp mode
The mode for the time stamp can be set via parameter p3100.
p3100 = 0
Time stamp based on operating hours
p3100 = 1
Time stamp UTC format
p3100 = 2
Time stamp operating hours + 01.01.2000
As of Firmware V4.7: With this setting the value in p3102 is used as the time stamp for
the error messages. For firmware versions prior to V4.7 the time basis of p2114 was used
with the setting p3100 = 0.
Note
Time stamp settings depending on the firmware version
If a project is upgraded from firmware V4.6 to V4.7 then the time stamp settings for the old
project are retained. The times displayed for the error messages do not therefore differ from
those in the old firmware version.
If a new
project is created in firmware version V4.7 and above, the factory setting for the
p3100
= 2 and therefore a different time basis for error messages. If the behavior desired is
the one for older versions than V4.7 then p3100 = 0 should be set.
Note
Synchronizing time stamps
If a control system and several drive devices are connected through a bus, then the different
time stamps can be synchronized to the time stamp of the control system (=time master).
Detailed information is provided in Chapter
Time synchronization between the control and
converter
(Page 905).

Table of Contents

Other manuals for Siemens SIROTEC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIROTEC and is the answer not in the manual?

Siemens SIROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIROTEC
CategoryDC Drives
LanguageEnglish

Related product manuals