Function modules
8.8 Basic positioner
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
515
The limitation is effective for the following activities:
● Jog mode
● Processing traversing blocks
● Direct setpoint specification / MDI for positioning and setting up
● Reference point approach
● Stop responses due to alarms
Jerk limitation is not active when messages are generated with stop responses OFF1 / OFF2
/ OFF3.
Starting against a closed brake
Under EPOS, if the drive should start against a closed brake, for example, for a suspended
load, then the enable signal p0899.2 is briefly withdrawn. The drive pulses are canceled and
fault F07490 is output.
To avoid this happening, using p1513 activate a supplementary torque which corresponds to
the brake holding torque. As a result, after releasing the brake, the load cannot sag and the
drive remains in closed-loop control without fault F07490 being output.
Function diagrams (see SINAMICS S120/S150 List Manual)
3630
- Traversing range limits (r0108.4 = 1)
Overview of important parameters (see SINAMICS S120/S150 List Manual)
p2571
p2572
EPOS maximum acceleration
p2573
p2646
CI: EPOS velocity override
p2578
re limit switch, minus signal source
p2579
CI: EPOS software limit switch, plus signal source
p2580
CO: EPOS software limit switch, minus
p2581
CO: EPOS software limit switch, plus
p2582
BI: EPOS software limit switch activation
r2683.0...14
OS status word 1