Function modules
8.8 Basic positioner
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
547
Cam switching signal 1 (r2683.8)
Cam switching signal 2 (r2683.9)
The electronic cam function can be implemented using these signals. Cam switching signal 1
is 0 if the actual position is greater than p2547 - otherwise 1. Cam switching signal 2 is 0 if
the actual position is greater than p2548 - otherwise 1. This means that the signal is deleted
if the drive is located behind (after) the cam switching position. The position controller
initiates these signals.
Direct output 1 (r2683.10)
Direct output 2 (r2683.11)
If a digital output is parameterized, the function "direct output 1" or "direct output 2", then it
can be set by a corresponding command in the traversing task (SET_O) or reset
(RESET_O).
Following error in tolerance (r2684.8)
When the axis is traversed, closed-loop position controlled, using a model, the permissible
following error is determined from the instantaneous velocity and the selected Kv factor.
Parameter p2546 defines a dynamic following error window that defines the permissible
deviation from the calculated value. The status signal indicates as to whether the following
error is within the window (status 1).
Target position reached (r2684.10)
The status signal "target position reached" indicates that the drive has reached its target
position at the end of a traversing command. This signal is set as soon as the actual drive
position is within the positioning window p2544 and is reset, if it leaves this window.
The status signal is not set, if
Signal level 1 at binector input p2554 "signal traversing command active".
Signal level 0 at binector input p2551 "signal setpoint static".
The status signal remains set, until
Signal level 1 at binector input p2551 "signal setpoint static".
Reference point set (r2684.11)
The signal is set as soon as referencing has been successfully completed. It is deleted as
soon as no reference is there or at the start of the reference point approach.

Table of Contents

Other manuals for Siemens SIROTEC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIROTEC and is the answer not in the manual?

Siemens SIROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIROTEC
CategoryDC Drives
LanguageEnglish

Related product manuals