Function modules
8.9 Master/slave function for Active Infeed
Drive functions
550 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Features
The "master/slave" function only works in conjunction with Active Line Modules.
One Active Line Module is the master and up to three others are slaves.
If the master fails, a slave ALM takes on the role of the master.
The redundant infeeds can continue functioning normally even if one infeed train has
failed.
Electrical isolation between the infeed trains is needed on the line side to prevent
circulating currents caused by non-synchronous pulsing patterns.
The entire infeed system supplies a joint DC busbar (DC link).
Since the Active Line Module cannot detect whether the DC link is disconnected or a DC-
link fuse has blown, an additional circuit to monitor these states must be installed (DC
breaker checkback function and fuse signaling contacts).
The higher-level controller communicates with the CUs and Active Line Modules via
PROFIBUS/PROFINET or analog data. If a higher-level controller is not to be used, the
control signals must be hard-wired (e.g. via TM31).
Infeed trains with different outputs can be combined.

Table of Contents

Other manuals for Siemens SIROTEC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIROTEC and is the answer not in the manual?

Siemens SIROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIROTEC
CategoryDC Drives
LanguageEnglish

Related product manuals