Monitoring functions and protective functions
9.2 Thermal monitoring and overload responses
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
637
Overload responses
The power unit responds with alarm A07805. The Control Unit initiates the parameterized
responses via p0290 at the same time that the alarm is issued. Possible responses include:
Reducing the pulse frequency (p0290 = 2, 3)
This is a highly effective method of reducing losses in the power unit, since switching
losses account for a high proportion of the total losses. In many applications, a temporary
reduction in pulse frequency is tolerable in order to maintain the process.
Disadvantage:
Reducing the pulse frequency increases the current ripple which, in turn, can increase the
torque ripple on the motor shaft (with low inertia load), thereby increasing the noise level.
Reducing the pulse frequency does not affect the dynamic response of the current control
circuit, since the sampling time for the current control circuit remains constant.
Reducing the output current (p0290 = 0, 2)
This variant is recommended when you do not need to reduce the pulse frequency or the
pulse frequency has already been set to the lowest level. Further, the load should also
have a characteristic similar to the fan, that is, a quadratic torque characteristic with
falling speed. Reducing the converter output current reduces the losses in the power unit.
No reduction (p0290 = 1)
You should choose this option if it is neither possible to reduce the pulse frequency nor
reduce the output current. The converter does not change its operating point once an
alarm threshold has been overshot, which means that the drive can be operated until it
reaches its shutdown values. Once it reaches its shutdown threshold, the converter
switches itself off with alarm A05000 (power unit: Overtemperature inverter heat sink),
A05001 (power unit: Overtemperature chip) or A07805 (drive: Power unit overload I2t).
The time until shutdown, however, is not defined and depends on the degree of overload.
Function diagrams (see SINAMICS S120/S150 List Manual)
8021
Signal
s and monitoring functions - thermal monitoring power unit
Overview of important parameters (see SINAMICS S120/S150 List Manual)
r0036
CO: Power unit overload I2t
r0037[0...19]
CO: Power unit temperatures
p0290
Power unit overload response
p0294
Power
Module warning I2t overload

Table of Contents

Other manuals for Siemens SIROTEC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIROTEC and is the answer not in the manual?

Siemens SIROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIROTEC
CategoryDC Drives
LanguageEnglish

Related product manuals