EasyManuals Logo

Siemens SIROTEC Function Manual

Siemens SIROTEC
1094 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #820 background imageLoading...
Page #820 background image
Communication
11.3 Communication via PROFINET IO
Drive functions
820 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Topology rules
Topology rules for RT
A topology can be, but need not be configured for RT. If a topology has been configured,
the devices must be wired in accordance with the topology.
Otherwise, the wiring between devices is entirely optional.
Topology rules for IRT
Mixed operation is not supported by STEP 7 V5.4 SP4, i.e. IRT "high performance"
cannot be combined with IRT "high flexibility" in the same synchronization domain.
A synchronization domain with IRT "high performance" can contain a maximum of one
IRT "high performance" island. "Island" means that the devices must be interconnected to
match the configured topology. A synchronization master must be positioned in the
relevant island.
IRT "high flexibility" is subject to the same topology rules as for IRT "high performance",
the only exception being that a topology does not need to be configured. However, if a
topology has been configured, the devices must be wired to match the topology.
Device selection in HW Config
Hardware catalog:
The drive unit from the appropriate device family entry in the hardware catalog must be
configured. For the real-time class IRT, these are all entries as of firmware version V2.5.
GSDML:
GSDML files for devices which contain IRT as of firmware version V2.5.

Table of Contents

Other manuals for Siemens SIROTEC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIROTEC and is the answer not in the manual?

Siemens SIROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIROTEC
CategoryDC Drives
LanguageEnglish

Related product manuals