EasyManuals Logo

Siemens SIROTEC Function Manual

Siemens SIROTEC
1094 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #920 background imageLoading...
Page #920 background image
Applications
12.4 Quick stop in the event of a power failure or emergency stop (servo)
Drive functions
920 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
In addition to the component wiring shown above, each drive object that is to carry out a
quick stop if the power fails needs to be parameterized. If parameterization is not carried out,
the drive coasts down once a DC link undervoltage has been identified (OFF2). To
implement the OFF3 function (quick stop), the following parameters need to be set:
p1240 = 5 (activates Vdc_min monitoring)
As well as the DC link monitor, which is always active, this activates another variable
alarm threshold, which should be set to a value above the undervoltage shutdown
threshold of 360 V ±2 % in p1248.
p1248 ≤ 570 V (for Active Line Modules)
p1248 ≤ 510 V (for Smart Line Modules)
This alarm level (in volts) indicates that the set value has been fallen below. Fault F07403
is triggered when this threshold is reached.
p2100[x] = 7403
Here you change the response to fault F07403.
p2101[x] = 3 (OFF3) response to the fault entered in p2100[x]

Table of Contents

Other manuals for Siemens SIROTEC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIROTEC and is the answer not in the manual?

Siemens SIROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIROTEC
CategoryDC Drives
LanguageEnglish

Related product manuals