B.3 Parameter Table
396 YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
■ U5: PI Monitors
U4-21
(7DDH)
Run Command Source
Selection
Displays the source for the Run command as XY-nn.
X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
2 = Reference 2 (b1-16)
Y: Input power supply data
0 = Digital operator
1 = External terminals
3 = MEMOBUS/Modbus communications
4 = Communication option card
7 = DWEZ
nn: Run command limit status data
00: No limit status.
01: Run command was left on when stopped in the PRG mode
02: Run command was left on when switching from LOCAL to REMOTE operation
03: Waiting for soft charge bypass contactor after power up (Uv or Uv1 flashes after 10 s)
04: Waiting for “Run command prohibited” time period to end
05: Fast Stop (digital input, digital operator)
06: b1-17 (Run command given at power-up)
07: During baseblock while coast to stop with timer
08: Frequency reference is below minimal reference during baseblock
09: Waiting for Enter command
No signal output
available
––
U4-22
(7DEH)
MEMOBUS/Modbus
Communications Reference
Displays the drive control data set by MEMOBUS/Modbus communications register no. 0001H
as a four-digit hexadecimal number.
No signal output
available
––
U4-23
(7DFH)
Communication Option Card
Reference
Displays drive control data set by an option card as a four-digit hexadecimal number.
No signal output
available
––
U4-32
(7FBH)
Option Card Reference
Displays the motor temperature (NTC).
U4-32 will display 20°C when a multi-function analog input is not set for motor thermistor
input (H1- = 17H).
Note: This parameter is available in models CIMR-E4A0930 and 4A1200.
200°C1°C–
U4-37
(1044H)
oH Alarm Location Monitor
Displays the module where the oH alarm occurred as a binary number.
Note: This parameter is available in models CIMR-E4A0930 and 4A1200.
No signal output
available
––
U4-38
(1045H)
FAn Alarm Location Monitor
Displays the module where the FAn alarm occurred as a binary number.
Note: This parameter is available in models CIMR-E4A0930 and 4A1200.
No signal output
available
––
U4-39
(1046H)
voF Alarm Location Monitor
Displays the module where the voF alarm occurred as a binary number.
Note: This parameter is available in models CIMR-E4A0930 and 4A1200.
No signal output
available
––
<19> This value's number of decimal places depends on the drive model. The value will have two decimal places (0.01 A) if the drive model is
CIMR-E2A0004 to 2A0040, 4A0002 to 4A0023 and one decimal place (0.1 A) if the drive model is CIMR-E2A0056 to 2A0415, 4A0031
to 4A1200.
<50> When reading the value of this monitor via MEMOBUS/Modbus a value of 8192 is equal to 100% of the drive rated output current.
No. (Addr.) Name Description
Analog Output
Level
Unit Page
U5-01
(57H)
PI Feedback
Displays the PI feedback value.
10 V: 100% 0.01% –
U5-02
(63H)
PI Input
Displays the amount of PI input (deviation between PI setpoint and feedback).
10 V: 100% 0.01% –
U5-03
(64H)
PI Output
Displays PI control output.
10 V: 100% 0.01% –
U5-04
(65H)
PI Setpoint
Displays the PI setpoint.
10 V: 100% 0.01% –
U5-05
(7D2H)
PI Differential Feedback
Displays the 2nd PI feedback value if differential feedback is used (H3- = 16).
10 V: 100% 0.01% –
U5-06
(7D3H)
PI Adjusted Feedback
Displays the difference of both feedback values if differential feedback is used (U5-01 - U5-05).
If differential feedback is not used, then U5-01 and U5-06 will be the same.
10 V: 100% 0.01% –
U5-14
(86BH)
PI Output Upper 4 Digits
Displays Custom PI output. U5-14 shows the upper 4 digits.
No signal output
available
––
U5-15
(86CH)
PI Output Lower 4 Digits
Displays Custom PI output. U5-15 shows the lower 4 digits.
No signal output
available
––
No. (Addr.) Name Description
Analog Output
Level
Unit Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
SIEP_C710616_35.book 396 ページ 2015年11月30日 月曜日 午後2時2分