D.3 UL Standards
450 YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum
allowable temperature of 75°C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 40°C.
Closed-Loop Crimp Terminal Recommendations
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL approval requires the use of UL Listed
crimp terminals when wiring the drive main circuit terminals on models CIMR-E2A0110 to 2A0415 and 4A0058 to
4A1200. Use only crimping tools as specified by the crimp terminal manufacturer. Yaskawa recommends crimp
terminals made by JST and Tokyo DIP (or equivalent) for the insulation cap.
Table D.6 matches the wire gauges and terminal screw sizes with Yaskawa - recommended crimp terminals, tools, and
insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge and screw size
for your drive model. Place orders with a Yaskawa representatives or the Yaskawa sales department.
Table D.6 Closed-Loop Crimp Terminal Size
4A0515
<4>
R/L1, S/L2, T/L3 120 × 2P 95 to 150 3/0 × 4P 3/0 to 300 125 × 2P 80 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 150 × 2P 95 to 150 4/0 × 4P 3/0 to 300 150 × 2P 80 to 150
–, +1 70 to 150 1/0 to 300 60 × 4P 60 to 150
+3 70 to 150 1/0 to 300 100 × 2P 60 to 150
150 50 to 150 1/0 1/0 to 300 60 50 to 150
4A0675
<4>
R/L1, S/L2, T/L3 95 × 4P 95 to 150 300 × 4P 4/0 to 300 80 × 4P 80 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 95 × 4P 95 to 150 300 × 4P 4/0 to 300 80 × 4P 80 to 150
–, +1 70 to 150 1/0 to 300 125 × 4P 60 to 150
+3 70 to 150 1/0 to 300 60 × 4P 60 to 150
95 × 2P 60 to 150 2/0 2/0 to 300 60 70 to 150
4A0930
<4>
R/L1, S/L2, T/L3,
R1/L11, S1/L21,
T1/L31
120 × 4P 95 to 150 (4/0 × 4P) × 2 3/0 to 300 150 × 4P 125 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 120 × 4P 95 to 150 (4/0 × 4P) × 2 3/0 to 300 150 × 4P 125 to 150
–, +1 95 to 150 4/0 to 300 (125 × 4P) × 2 100 to 150
+3 95 to 150 4/0 to 300 125 × 4P 100 to 150
120 × 2P 70 to 120 3/0 3/0 to 250 100 80 to 125
4A1200
<4>
R/L1, S/L2, T/L3,
R1/L11, S1/L21,
T1/L31
(95 × 4P) × 2 95 to 150 (300 × 4P) × 2 4/0 to 300 (125 × 4P) × 2 100 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 (95 × 4P) × 2 95 to 150 (300 × 4P) × 2 4/0 to 300 (125 × 4P) × 2 100 to 150
–, +1 120 to 150 250 to 300 (150 × 4P) × 2 125 to 150
+3 95 to 150 4/0 to 300 (100 × 4P) × 2 100 to 150
95 × 4P 95 to 120 4/0 4/0 to 250 125 100 to 125
<1> Gauges listed here are for use in Europe and China.
<2> Gauges listed here are for use in the United States.
<3> Gauges listed here are for use in Asia except for China.
<4> Drive models CIMR-E4A0058 to 4A1200 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
Model
CIMR-E
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp Terminal
Model Number
Tool
Insulation Cap
Model No.
Code <2>
R/L1, S/L2,
T/L3
U/T1, V/T2,
W/T3
Machine No. Die Jaw
200 V Class
2A0004
2A0006
2A0008
2A0010
14
<1>
M4
R2-4
YA-4 AD-900
TP-003 100-054-028
12
R5.5-4 TP-005 100-054-029
10
2A0012
14 14
<1>
M4
R2-4
YA-4 AD-900
TP-003 100-054-028
12 <1> 12
R5.5-4 TP-005 100-054-029
10
2A0018
–14
M4
R2-4
YA-4 AD-900
TP-003 100-054-028
12
R5.5-4 TP-005 100-054-029
10
<1>
2A0021
12
M4 R5.5-4 YA-4 AD-900 TP-005 100-054-029
10
<1>
Model
CIMR-E
Terminal
For Europe and China <1> For U.S.A. <2> For Asia <3>
Screw
Size
Tightening
Torque
Nm (lb.in.)
Recommended
Gauge
mm
2
Applicable
Gauge
mm
2
Recommended
Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommended
Gauge
mm
2
Applicable
Gauge
mm
2
SIEP_C710616_35.book 450 ペー 2015年11月30日 月曜日 午後2時2分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA E1000 and is the answer not in the manual?

YASKAWA E1000 Specifications

General IconGeneral
BrandYASKAWA
ModelE1000
CategoryController
LanguageEnglish

Related product manuals