EasyManua.ls Logo

ADCMT 6166 - 5 Operational Descriptions; Connection with Load; Configuration of Output Terminals; 2-Wire and 4-Wire Connections

ADCMT 6166
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6166 DC Voltage Current Source Operation Manual
5. OPERATIONAL DESCRIPTIONS
5-1
5. OPERATIONAL DESCRIPTIONS
5.1 Connection with Load
5.1.1 Configuration of Output Terminals
The 6166 has four output terminals, two of which are positive terminals (red) and the other two are nega-
tive terminals (black). Both type of the terminals are divided into an OUTPUT terminal and a SENSE ter-
minal.
Normally, the OUTPUT terminals and the SENSE terminals are short-circuited (in 2-wire connection)
with the same polarity respectively. (The EXTERNAL SENSE key goes OFF.)
5.1.2 2-Wire and 4-Wire Connections
If there is considerable voltage drop due to cable resistance in the voltage ranges (1 V, 10 V, 100 V and
1000 V), connect the load in 4-wire connection. (The EXTERNAL SENSE key goes ON.)
The equivalent circuits used in 2-wire and 4-wire connections are shown on the next pages (Figure 5-1 and
Figure 5-2).
When the voltage is set to the full scale, the voltage sensing current (Is) is 40 A in the 1 V range or
100 A in the 10 V, 100 V and 1000 V ranges.
Thus, when the load current (Io) is less than the voltage sensing current (Is), using 2-wire connection offers
higher accuracy output.
For example, when connecting the load that has high impedance such as a digital multimeter, use 2-wire
connection.
On the contrary, when the load current (Io) is more than the voltage sensing current (Is), connect the load
in 4-wire connection (connect the OUTPUT and SENSE terminals at the load). This connection generates
an error due to the resistance of the cables connected to the SENSE terminals.
Table 5-1 shows the resistance of the cables connected to the SENSE terminals and the resulting error.
Table 5-2 shows the cable resistance per meter for reference.

Table of Contents

Related product manuals