Rockwell Automation Publication 5069-UM002A-EN-P - January 2019 137
Connect to Different EtherNet/IP Network Levels Chapter 6
You set the IP address and Subnet Mask on the Internet Protocol tab.
1. Confirm that the project is online.
2. Confirm that the controller is in one of the following modes:
Program mode
Remote Program mode
Remote Run mode
You cannot change the IP Address or Subnet Mask if the controller is in
Run mode.
3. Access the Controller Properties.
4. On the Internet Protocol tab, click Manually configure IP settings.
5. From the Port pull-down menu, choose A1.
6. Assign IP Address and Network Mask values, and click Apply.
7. Repeat the previous steps, beginning at
step 5
In
step 5, make sure that you choose A2 from the Port pull-down menu.
TIP When you set the IP address and Subnet Mask, we recommend that you use