AKD2G-S Installation Manual, Safety 1 | 9 Setup
9.3 Switch-On and Switch-Off Behavior
This chapter describes the switch-on and switch-off behavior of the AKD2G with STO.
Behavior of “holding brake” function
Drives with an enabled holding brake function have a special timing for switching on and off the output stage ( #
101). Events that remove the AXIS#.ACTIVE signal trigger the holding brake to apply. As with all electronic circuits,
the general rule applies that there is a possibility of the internal holding brake module failing.
If the drive detects the motor to be at zero velocity (as configured by AXIS#.ZEROT and AXIS#.ZEROV) or timeout
occurs during a stop procedure, the brake is applied. Set parameter AXIS#.MOTOR.BRAKEIMM to 1 with vertical
axes, to apply the motor holding brake ( # 101) immediately after faults or Hardware Disable.
Behavior when undervoltage condition is present
The behavior in an undervoltage condition depends on the VBUS.UVMODE setting.
VBUS.UVMODE DC Bus Undervoltage Mode. Consult the WorkBench Online Help for configuring the parameter.
0 The drive will report a F2007 undervoltage fault any time an undervoltage condition occurs.
1 (default)
The drive will report a warning W2007 if not enabled. The drive will report a fault if the drive is enabled
when the condition occurs, or an attempt is made to enable while an under voltage condition occurs.
Functional Safety
The drive can be secured to standstill with STO. Even when power is being supplied, the drive shaft is protected
against unintentional restart. The chapter “Functional Safety” describes how to use the safety functions ( # 180).
l
Functional safety, e.g. with hanging load (vertical axes), requires an additional brake, controlled for example from
the second axis or externally from a safety controller. The brakes can be mapped to an axis with WorkBench.
l
The Hardware Enable does not initiate a controlled stop but switches off the power stage immediately.
l
Set parameter AXIS#.MOTOR.BRAKEIMM to 1 with vertical axes, to apply the brake immediately after faults or
Hardware Disable.
170 Kollmorgen | kdn.kollmorgen.com | June, 2023

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kollmorgen AKD 2G-S Series and is the answer not in the manual?

Kollmorgen AKD 2G-S Series Specifications

General IconGeneral
BrandKollmorgen
ModelAKD 2G-S Series
CategoryServo Drives
LanguageEnglish

Related product manuals