C00989
C00990
C00991
C00992
Parameter | Name:
C00989 | Restart on the fly: Flying restart frequency fd_add
Data type: INTEGER_16
Index: 23586
d
= 5C22
h
From version 15.00.00
Flying restart fct.
Setting range (min. value | unit | max. value)
0.00 Hz 5.00
Subcodes Lenze setting Info
C00989/1 0.00 Hz Restart on the fly: Flying restart frequency fd_add
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00990 | Flying restart fct.: Activation
Data type: UNSIGNED_8
Index: 23585
d
= 5C21
h
Switch on/activate flying restart circuit for non-feedback drive systems
Flying restart fct.
Selection list (Lenze setting printed in bold)
0Off
1On
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00991 | Flying restart fct.: Process
Data type: UNSIGNED_16
Index: 23584
d
= 5C20
h
Selection of the starting value and the speed search range for the flying restart function
Flying restart fct.
Selection list (Lenze setting printed in bold) Info
0 0...+n | Start: +10 Hz Search positive speed range (0 ... +n) with a start
frequency of +10 Hz
1 -n...0 | Start: -10 Hz Search negative speed range (-n ... 0) with a start
frequency of -10 Hz
2 -n...+n | Start: +10 Hz Search negative and positive speed range (-n ... n) with a
start frequency of +10 Hz
3 -n...+n | Start: -10 Hz Search negative and positive speed range (-n ... n) with a
start frequency of -10 Hz
4 -n...+n | Start: Cx992 Search the negative and positive speed range (-n ... n)
with the start frequency set in C00992
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00992 | Flying restart fct.: Start frequency
Data type: INTEGER_16
Index: 23583
d
= 5C1F
h
Manual selection of the starting value for the flying restart function
•Only active if C00991
= 4
Flying restart fct.
Setting range (min. value | unit | max. value) Lenze setting
-200 Hz 200 10 Hz
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1