15 Parameter reference
15.2 Parameter list
1126
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C02295
C02296
C02297
Parameter | Name:
C02295 | LS_WriteParamList: Flying restart fct.: Activation
Data type: UNSIGNED_8
Index: 22280
d
= 5708
h
From version 12.00.00 onwards: Parameter values (1st value ... 4th value) for optional motor data change-over
Selection list
0Off
1On
Subcodes Lenze setting Info
C02295/1 0: Off LS_WriteParamList
: c990_val1
C02295/2 0: Off LS_WriteParamList
: c990_val2
C02295/3 0: Off LS_WriteParamList
: c990_val3
C02295/4 0: Off LS_WriteParamList
: c990_val4
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C02296 | LS_WriteParamList: Flying restart fct.: process
Data type: UNSIGNED_16
Index: 22279
d
= 5707
h
From version 12.00.00 onwards: Parameter values (1st value ... 4th value) for optional motor data change-over
Selection list
0 0...+n | Start: +10 Hz
1 -n...0 | Start: -10 Hz
2 -n...+n | Start: +10 Hz
3 -n...+n | Start: -10 Hz
4 -n...+n | Start: Cx992
Subcodes Lenze setting Info
C02296/1 2: -n...+n | Start: +10 Hz LS_WriteParamList
: c991_val1
C02296/2 2: -n...+n | Start: +10 Hz LS_WriteParamList
: c991_val2
C02296/3 2: -n...+n | Start: +10 Hz LS_WriteParamList
: c991_val3
C02296/4 2: -n...+n | Start: +10 Hz LS_WriteParamList: c991_val4
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C02297 | LS_WriteParamList: Flying restart: Start frequency
Data type: INTEGER_16
Index: 22278
d
= 5706
h
From version 12.00.00 onwards: Parameter values (1st value ... 4th value) for optional motor data change-over
Setting range (min. value | unit | max. value)
-200 Hz 200
Subcodes Lenze setting Info
C02297/1 10 Hz LS_WriteParamList
: c992_val1
C02297/2 10 Hz LS_WriteParamList
: c992_val2
C02297/3 10 Hz LS_WriteParamList
: c992_val3
C02297/4 10 Hz LS_WriteParamList
: c992_val4
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1