Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 1358
17 Function library
17.1 Function blocks | L_DFSET_1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01075/1 Synchronisation mode - mark
correction
0 Synchronisation inactive Lenze setting
1 Permanent synchronisation without
enable via the bZeroPulse input
Correction is executed over the
shortest possible path.
The synchronisation only takes place
after 2 setpoint pulses have been
received at the bSetTPReceived input.
(required pulse order: set-actual-set)
2 Permanent synchronisation only
with enable via the bZeroPulse input
•When bZeroPulse is set to TRUE, a
permanent zero pulse/touch
probe synchronisation is
executed.
Correction is executed over the
shortest possible path.
10 One-time synchronisation
An angular difference is
compensated over the shortest
possible path.
11 One-time synchronisation
An angle difference is
compensated in CW direction.
12 One-time synchronisation
An angular difference is
compensated in CCW direction.
13 One-time synchronisation
An angular difference is
compensated over the shortest
possible path.
Synchronisation takes place after the
first setpoint pulse has been received
at the bSetTPReceived input and/or
actual value pulse at the
bActTPReceived input.
(Required clock sequence: Set/actual
or actual/set)
Parameters Possible settings Info