Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 1462
17 Function library
17.1 Function blocks | L_PCTRL_1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
nSet_a
INT
Sensor and process setpoint for operating modes 2, 4 and 5
• Scaling: 16384 ≡ 100 %
• Internal limitation to ± 199.99 %
• Display parameter: C00830/63
nAct_a
INT
Speed or actual sensor value (actual process value)
• Scaling: 16384 ≡ 100 %
• Internal limitation to ± 199.99 %
• Display parameter: C00830/61
bInAct
BOOL
Deactivate process controller temporarily (stop)
• Changes can be done online.
• Display parameter: C00833/76
Note: This input is not interconnected in the LA_NCtrl application block.
TRUE • The current output value is frozen.
• The internal control algorithm is stopped.
• However, a setpoint selected via input nNSet_a is still provided in
operating modes 0/1/4/5.
bIOff
BOOL
Switch off the I-component of the process controller
• Changes can be done online.
• Display parameter: C00833/77
TRUE The I component of the process controller is set to zero.
nInfluence_a
INT
Limitation of the influencing factor in percent
• nInfluence_a serves to limit the influencing factor of the PID controller contained
in the FB to a required value (- 199.99 % ... + 199.99 %).
• Scaling: 16384 ≡ 100 %
• Internal limitation to ± 199.99 %
• Display parameter: C00830/64
bEnableInfluenceRamp
BOOL
Activate ramp for influencing factor
• Display parameter: C00833/106
TRUE Influencing factor of the PID controller is ramped up to the
nInfluence_a value.
FALSE Influencing factor of the PID controller is ramped down to "0".
bISet
BOOL
Accept I component nISet_a in PID controller
TRUE The value at the input nISet_a is accepted in the PID controller.
nISet_a
INT
Selection of I component of PID controller
• With a TRUE signal at bISet, the assigned value is accepted in the PID controller.
• Scaling: 16384 ≡ 100 %
• Internal limitation to ± 199.99 %
bPIDOff
BOOL
(from version 06.00.00)
Reset the entire PID controller
TRUE • The I component of the controller is set to zero.
• The controller output is set to zero.
• The internal control algorithm is stopped.
Designator
Data type
Information/possible settings