15 Parameter reference
15.2 Parameter list
922
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00579
C00580
C00581
Parameter | Name:
C00579 | Resp. to max. speed/output freq. reached
Data type: UNSIGNED_8
Index: 23996
d
= 5DBC
h
Response when the max. speed limit (C00909) or output frequency limit (C00910) has been reached.
Selection list (Lenze setting printed in bold)
0No Reaction
1Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00580 | Resp. to operating system error
Data type: UNSIGNED_8
Index: 23995
d
= 5DBB
h
From version 11.00.00
Response if the required computing time of the application exceeds the available computing time.
Selection list
0 No Reaction
1Fault
5 Warning
Subcodes Lenze setting Info
C00580/1 0: No Reaction Resp. to runtime exceedance
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00581 | Resp. to LS_SetError_x
Data type: UNSIGNED_8
Index: 23994
d
= 5DBA
h
Selection of the error responses for application error messages
• An application error message is tripped by a FALSE/TRUE edge at the binary inputs bSetError1...4.
Selection list
0 No Reaction
1Fault
2Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information
Subcodes Lenze setting Info
C00581/1 0: No Reaction LS_SetError_1
: Resp. to bSetError1
C00581/2 0: No Reaction LS_SetError_1
: Resp. to bSetError2
C00581/3 0: No Reaction LS_SetError_1
: Resp. to bSetError3
C00581/4 0: No Reaction LS_SetError_1
: Resp. to bSetError4
C00581/5 0: No Reaction LS_SetError_2
: Resp. to bSetError1
C00581/6 0: No Reaction LS_SetError_2
: Resp. to bSetError2
C00581/7 0: No Reaction LS_SetError_2
: Resp. to bSetError3
C00581/8 0: No Reaction LS_SetError_2
: Resp. to bSetError4
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1