15 Parameter reference
15.2 Parameter list
928
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00600
C00601
C00602
C00604
Parameter | Name:
C00600 | Resp. to DC bus voltage
Data type: UNSIGNED_8
Index: 23975
d
= 5DA7
h
Configuration of monitoring of the motor control (group 3)
Selection list
1Fault
2Trouble
Subcodes Lenze setting Info
C00600/1 2: Trouble Response to DC bus undervoltage
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00601 | Del. resp. to fault: DC bus overvoltage
Data type: UNSIGNED_16
Index: 23974
d
= 5DA6
h
Error response delay times
Setting range (min. value | unit | max. value)
0.000 s 65.000
Subcodes Lenze setting Info
C00601/1 2.000 s Delay time for triggering the "DC-bus overvoltage" error
• If a DC-bus overvoltage occurs, an error will not be
triggered until the set delay time has elapsed.
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000
Parameter | Name:
C00602 | Resp. to earth fault
Data type: UNSIGNED_8
Index: 23973
d
= 5DA5
h
Response to earth fault in the motor phase(s)
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00604 | Resp. to device overload (Ixt)
Data type: UNSIGNED_8
Index: 23971
d
= 5DA3
h
Response if the adjustable device utilisation threshold (C00123) is reached.
• The current device utilisation is displayed in C00064
.
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1