Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 971
15 Parameter reference
15.2 Parameter list
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00802
C00803
C00804
C00805
Parameter | Name:
C00802 | L_MPot_1: Acceleration time
Data type: UNSIGNED_16
Index: 23773
d
= 5CDD
h
The L_MPot_1 FB: Acceleration time of the motor potentiometer function
Setting range (min. value | unit | max. value) Lenze setting
0.1 s 6000.0 10.0 s
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 10
Parameter | Name:
C00803 | L_MPot_1: Deceleration time
Data type: UNSIGNED_16
Index: 23772
d
= 5CDC
h
The L_MPot_1 FB: Deceleration time of the motor potentiometer function
Setting range (min. value | unit | max. value) Lenze setting
0.1 s 6000.0 10.0 s
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 10
Parameter | Name:
C00804 | L_MPot_1: Inactive fct.
Data type: UNSIGNED_8
Index: 23771
d
= 5CDB
h
The L_MPot_1 FB: Selection of the response if the motor potentiometer is deactivated via input bInAct
Selection list (Lenze setting printed in bold) Info
0 Retain value Keep output value
1 Deceleration to 0 Deceleration via ramp to 0
2 Deceleration to lower limit Deceleration via ramp to the lower limit (C00801
)
3 Without ramp to 0 Step change to 0
4 Without ramp to lower limit Jump to lower limit (C00800
)
5 Acceleration to upper limit Acceleration via ramp to upper limit (C00800
)
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00805 | L_MPot_1: Init fct.
Data type: UNSIGNED_8
Index: 23770
d
= 5CDA
h
The L_MPot_1 FB: Selection of the response at device switch-on
Selection list (Lenze setting printed in bold)
0 Load last value
1 Load lower limit
2Load 0
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1