1. Select and conrm the analog output.
2. Press the [Adjust] softkey.
The window for the 1st value opens.
3. Enter and conrm e.g.the value for 4 mA measured by the connected PLC under
[Measured].
The window for the 2nd value opens.
X3 Process Indicator PR 5410 9 Extended functions
Minebea Intec EN-268