Function Code Parameter Name Setting Range Default
Unit Property
F8-03 Drive gain 0.00–2.00 0.60 -
★
F8-04 Brake gain 0.00–2.00 0.60 -
★
These two parameters are used to set the pre-torque gain when the elevator runs on the
drive side or the brake side.
For details, see section 5.1.5.
Function Code Parameter Name Setting Range Default Unit Property
F8-05 Current car load 0–255 0 -
●
This parameter is read-only and reects the load situation in the car. The value is sampled
by the NICE1000
new
by using a load cell. This parameter is used to judge overload or full-
load, or calculate the torque current for load cell pre-torque compensation.
Function Code Parameter Name Setting Range Default Unit Property
F8-06 Car no-load load 0–255 0 -
★
F8-07 Car full-load load 0–255 100 -
★
These two parameters respectively specify the car no-load load and full-load load. They are AD
sampling values.
If F8-06 = F8-07, the full-load and overload become invalid.
Function Code Parameter Name Setting Range Default Unit Property
F8-08
Load cell input
selection
0: MCB digital sampling
1: MCB analog sampling
0 -
☆
It is used to set the channel of elevator load cell signals. Set this parameter correctly before
using the load cell device.
Function Code Parameter Name Setting Range Default Unit Property
F8-09
Emergency evacuation
operation speed at power failure
0.000 to F3-11 0.050 m/s
★
It is used to set the speed for emergency evacuation operation at power failure.
Function Code Parameter Name Setting Range Default Unit Property
F8-10
Emergency evacuation
operation mode at power failure
0–2 0 -
★
It is used to set the emergency evacuation operation mode at power failure.
•
0: Motor not running
•
1: UPS
•
2: 48 V battery power supply