Description of Function Codes NICE1000
new
User Manual
- 160 -
Function Code Parameter Name Setting Range Default Unit Property
Fb-02
Service oors of door
machine 1
0–65535 65535 -
Fb-04
Service oors of door
machine 2
0–65535 65535 -
These parameters are used to set the service oors of door machine 1 and door machine 2.
These parameters are set in the same way as F6-05. For details, refer to F6-05.
Function Code Parameter Name Setting Range Default Unit Property
Fb-03
Holding time of manual door
open
1–60 10 s
It is used to set the delay time after door open limit under manual control. This parameter is
valid only the manual door function is used.
Function Code Parameter Name Setting Range Default Unit Property
Fb-06 Door open protection time 5–99 10 s
It is used to set the door open protection time.
After outputting the door open command, if the system does not receive the door open limit
signal after the time set in this parameter, the system re-opens the door. When the door
open/close times reach the value set in Fb-09, the system reports fault Err48.
Function Code Parameter Name Setting Range Default Unit Property
Fb-07 Program control selection 0–65535 0 -
It is used to select the required program control functions.
Each bit of the function code denes a function, as described in the following table.
If a bit is set to 1, the function indicated by this bit is enabled; if this bit is set to 0, the
function is disabled.
For details on how to view and set this function code in bit, refer to F6-06.
Table 7-16 Program control functions indicated by bits of Fb-07
Fb-07 Program control selection
Bit Function Description Default
Bit5
Synchronous motor
current detection
The system detects the output current at startup of the
synchronous motor, and blocks the output and forbids
running if the current is abnormal.
0
Bit13
Higher voltage/
Lower voltage 1.5s
detection
When the higher voltage/lower voltage safety and
door lock signals are set, the higher voltage and
lower voltage signals must be consistent within 1.5s.
Otherwise, the system considers that the signals are
invalid. You need to power on the system again and
then the system restores the detection.
0