F3-14 (Zero-speed control time at startup) specifies the time from output of the RUN
contactor to output of the brake contactor, during which the controller performs excitation
on the motor and outputs zero-speed current with large startup torque.
•
F3-15 (Brake release delay) species the time from the moment when the system sends
the brake release command to the moment when the brake is completely released, during
which the system retains the zero-speed torque current output.
•
F3-16 (Zero-speed control time at end) species the zero-speed output time when the
running curve ends.
•
F8-11 (Brake apply delay) species the time from the moment when the system sends the
brake apply command to the moment when the brake is completely applied, during which
the system retains the zero-speed torque current output.
Figure 7-3 Running time sequence
Function Code Parameter Name Setting Range Default Unit Property
F3-17 Low-speed re-leveling speed 0.080 to F3-11 0.100 m/s
★
It is used to set the elevator speed of returning to the leveling position at normal non-leveling
stop.
Function Code Parameter Name Setting Range Default Unit Property
F3-18
Acceleration rate at
emergency evacuation
0.100–1.300 0.300 m/s
2
★
It is used to set the acceleration rate at emergency evacuation.
Group F4: Floor Parameters
Function Code Parameter Name Setting Range Default Unit Property
F4-00 Leveling adjustment 0–60 30 mm
★