- 117 -
Function Code Parameter Name Setting Range Default Unit Property
F3-08 Special deceleration rate 0.200–2.000 0.500 m/s
2
★
It is used to set the deceleration rate in elevator slow-down, inspection, and shaft auto-tuning.
This parameter is not used during normal running. It is used only when the elevator position
is abnormal or the slow-down signal is abnormal, preventing over travel top terminal or over
travel bottom terminal.
Function Code Parameter Name Setting Range Default Unit Property
F3-09 Pre-deceleration distance 0–90.0 0.0 mm
★
It is used to set the pre-deceleration distance of the elevator in distance control, as shown
in Figure 7-2. This function is to eliminate the effect of encoder signal loss or leveling signal
delay.
Function Code Parameter Name Setting Range Default Unit Property
F3-10 Re-leveling speed 0.000–0.080 0.040 m/s
★
is used to set the elevator speed during re-leveling.
This parameter is valid only when the pre-open module (MCTC-SCB-A) is added to
implement the re-leveling function (set in FE-13).
Function Code Parameter Name Setting Range Default Unit Property
F3-11 Inspection speed 0.100–0.500 0.250 m/s
★
It is used to set the elevator speed during inspection and shaft auto-tuning.
Function Code Parameter Name Setting Range Default Unit Property
F3-12 Position of up slow-down 0.000–300.00 0.00 m
★
F3-13 Position of down slow-down 0.000–300.00 0.00 m
★
These parameters specify the positions of the slow-down switches relative to the bottom
leveling position, and the positions are automatically recorded during shaft auto-tuning. For
the installation positions of the slow-down switches, see Table 3-11.
The NICE1000
new
integrated elevator controller supports only one pair of slow-down
switches, which are installed near the terminal oor.
The system automatically detects the speed when the elevator reaches a slow-down switch.
If the detected speed or position is abnormal, the system enables the elevator to slow down
at the special deceleration rate set in F3-08, preventing over travel top terminal or over
travel bottom terminal.
Function Code Parameter Name Setting Range Default Unit Property
F3-14 Zero-speed control time at startup 0.000–1.000 0.200 s
★
F3-15 Brake release delay 0.000–2.000 0.600 s
★
F3-16 Zero-speed control time at end 0.000–1.000 0.300 s
★
These parameters are used to set the time related to the zero-speed holding current output
and braking action delay.