- 169 -
Table 7-18 Elevator functions indicated by bits of FE-13
FE-13 Elevator function selection 1
Bit Function Description Default
Bit2 Re-leveling function
The elevator performs re-leveling at a low speed
with door open. An external shorting door lock circuit
contactor needs to be used together.
0
Bit3
Door pre-open
function
During normal stop, when the elevator speed is
smaller than a certain value and the door zone signal
is active, the system shorts the door lock by means of
the shorting door lock circuit contactor and outputs the
door open signal, implementing door pre-open. This
improves the elevator use efciency.
0
Bit5 Forced door close
If the door still does not close within the time set in Fb-
17 in automatic state, the system outputs the forced
door close signal; at this moment, the light curtain
becomes invalid and the buzzer tweets.
0
Bit6
Door open valid at
non-door zone in
the inspection state
In the inspection state, you can open/close the door by
pressing the door open/close button at the non-door
zone.
0
Bit7
Door open and
close once after
inspection turned to
normal
The elevator door opens and closes once after the
system turns from rst-time inspection to normal
running.
0
Bit9
Independent
running
The independent running function is enabled. 0
Bit11
Door re-open after
car call of the
present oor
The door re-opens if the car call of the present oor is
valid during door close.
1
Function Code Parameter Name Setting Range Default Unit Property
FE-14 Elevator function selection 2 0–65535 0 -
☆
It is used to set the elevator functions. "1" indicates that the function is enabled, and "0"
indicates that the function is disabled.
It is used to set the elevator functions.
Each bit of the function code denes a function, as described in the following table.
If a bit is set to 1, the function indicated by this bit is enabled; if this bit is set to 0, the
function is disabled.
For details on how to view and set this function code in bit, refer to F6-06.
Table 7-19 Elevator functions indicated by bits of FE-14
FE-14 Elevator Function Selection 2
Bit Function Description Default
Bit1
Door open holding
at open limit
The system still outputs the door open command
upon door open limit.
0