System Commissioning and Application Example NICE1000
new
User Manual
- 76 -
5.2.2 Parallel Control of Two Elevators
The NICE1000
new
supports parallel control of two elevators, which is implemented by using
the CANbus communication port for information exchange and processing between the two
elevators, improving elevator use efciency.
Parameter Setting
Function Code Parameter Name Setting Range Setting in Parallel Control
Fd-03
Number of elevators in
parallel control mode
1–2 2
Fd-04 Elevator No. 1–2
Master elevator: 1
Slave elevator: 2
Wiring for Parallel Control Communication
Connect the CN3 terminals of the controllers for the two elevators, as shown in the following
gure.
Figure 5-12 Wiring for parallel control communication
NICE1000
new
CN3
NICE1000
new
CN3
Elevator 1#
Elevator 2#
CAN
+
CAN-
GND
CAN communication
cable for parallel control
CAN+
CAN-
GND
Function Description
Physical oor, relative to the NICE control system, is dened by the installation position of
the leveling plate. The oor (such as the ground oor) at which the lowest leveling plate is
installed corresponds to physical oor 1. The top physical oor is the accumulative number
of the leveling plates. In parallel mode, the physical oor numbers of the same oor for two
elevators are consistent.
If the oor structures of two elevators are different, the physical oor numbers should start
with the oor with the lowest position. The physical oors at the overlapped area of the two
elevators are the same. Even if one elevator does not stop a oor in the overlapped area, a
leveling plate should be installed there. You can make the elevator not stop at the oor by
setting service oors.
When two elevators are in parallel mode, the hall call and car call wiring and setting should
be performed according to physical oors. Parallel running can be implemented only when
the hall call and car call setting for one elevator is the same as that for the other elevator in
terms of the same oor.
Note
In parallel mode, the top oor (F6-00) and bottom oor (F6-01) of the elevators should be set
based on corresponding physical oors.