EasyManuals Logo

Monarch NICE1000 User Manual

Monarch NICE1000
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #199 background imageLoading...
Page #199 background image
NICE1000
new
User Manual EMC
- 197 -
Figure 9-1 Grounding of the shielded cable
The shield must
be grounded.
9.4.2 Installation Precautions of the Shielded Cable
Symmetrical shielded cable is recommended. The four-conductor shielded cable can also
be used as an input cable.
The motor cable and PE shielded conducting wire (twisted shielded) should be as short
as possible to reduce electromagnetic radiation and external stray current and capacitive
current of the cable. If the motor cable is over 100 meters long, an output lter or reactor
is required.
It is recommended that all control cables be shielded.
It is recommended that a shielded cable be used as the output power cable of the
controller; the cable shield must be well grounded. For devices suffering from interference,
shielded twisted pair (STP) cable is recommended as the lead wire and the cable shield
must be well grounded.
9.4.3 Cabling Requirement
1. The motor cables must be laid far away from other cables, with recommended distance
larger than 0.5 m. The motor cables of several controllers can be laid side by side.
2. It is recommended that the motor cables, power input cables and control cables be laid
in different ducts. To avoid electromagnetic interference caused by rapid change of the
output voltage of the controller, the motor cables and other cables must not be laid side
by side for a long distance.
3. If the control cable must run across the power cable, make sure they are arranged at an
angle of close to 90°. Other cables must not run across the controller.
4. The power input and output cables of the controller and weak-current signal cables
(such as control cable) should be laid vertically (if possible) rather than in parallel.
5. The cable ducts must be in good connection and well grounded. Aluminium ducts can
be used to improve electric potential.
6. The filter and controller should be connected to the cabinet properly, with spraying
protection at the installation part and conductive metal in full contact.
7. The motor should be connected to the system (machinery or appliance) properly, with
spraying protection at the installation part and conductive metal in full contact.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Monarch NICE1000 and is the answer not in the manual?

Monarch NICE1000 Specifications

General IconGeneral
BrandMonarch
ModelNICE1000
CategoryController
LanguageEnglish

Related product manuals