Function Code Parameter Name Setting Range Default Unit Property
Fb-08 Door close protection time 5–99 15 s
☆
It is used to set the door close protection time.
After outputting the door close command, if the system does not receive the door close limit
signal after the time set in this parameter, the system re-closes the door. When the door
open/close times reach the value set in Fb-09, the system reports fault Err49.
Function Code Parameter Name Setting Range Default Unit Property
Fb-09
Door open/close
protection times
0–20 0 -
☆
It is used to set the door re-open/re-close times allowed when door open/close is abnormal.
Function Code Parameter Name Setting Range Default Unit Property
Fb-10 Door state of standby elevator 0–2 0 -
☆
It is used to set the door state when the elevator is in stop and standby state.
The values are as follows:
•
0: Closing the door as normal at base oor
•
1: Waiting with door open at base oor
•
2: Waiting with door open at each oor
Function Code Parameter Name Setting Range Default Unit Property
Fb-11
Door open holding
time for hall call
1–1000 5 s
☆
It is used to set the door open holding time when there is a hall call. The elevator closes the
door immediately after receiving a door close command.
Function Code Parameter Name Setting Range Default Unit Property
Fb-12
Door open holding
time for car call
1–1000 3 s
☆
It is used to set the door open holding time when there is a car call. The elevator closes the
door immediately after receiving a door close command.
Function Code Parameter Name Setting Range Default Unit Property
Fb-13
Door open holding time upon
open delay valid
10–1000 30 s
☆
It is used to set the door open holding time when there is door open delay input. The
elevator closes the door immediately after receiving a door close command.
Function Code Parameter Name Setting Range Default Unit Property
Fb-14
Door open holding
time at base oor
1–1000 10 s
☆