NICE1000
new
User Manual Description of Function Codes
- 147 -
For details, see section 5.2.1.
Function Code Parameter Name Setting Range Default Unit Property
F8-11 Brake apply delay 0.200–1.500 0.200 s
It is used to set the time from the moment when the system sends the brake apply command
to the moment when the brake is completely applied. For details, see Figure 7-3.
Function Code Parameter Name Setting Range Default Unit Property
F8-12 Fire emergency oor 2 0 to F6-00 0 -
It is used to set the second re emergency oor. The switchover between re emergency
oor 1 and re emergency oor 2 is implemented by means of input from the MCB. When
this signal is input, the elevator enters the re emergency state and returns to this oor.
Function Code Parameter Name Setting Range Default Unit Property
F8-13
Anti-nuisance
function
Bit0: Disabled
Bit1: Judged by light curtain
Bit 2: Judged by light-load
signal
0 -
It is the criteria for judging whether nuisance exists.
Bit0: Anti-nuisance function disabled
Bit1: Nuisance judged by light curtain
The system determines that nuisance exists when the light curtain does not act after the
elevator stops at arrival for three consecutive times.
Bit2: Nuisance judged by light-load signal
If the light-load signal is active, the system determines that nuisance exists when the
number of car calls is greater than a certain value.
When the system determines that the elevator is in the nuisance state, it cancels all car
calls. In this case, call calls need to be registered again.
Group F9: Time Parameters
Function Code Parameter Name Setting Range Default Unit Property
F9-00
Idle time before
returning to base oor
0–240 10 min
It is used to set the idle time of the elevator before returning to the base oor.
When the idle time of the elevator exceeds the setting of this parameter, the elevator returns
to the base oor.
If this parameter is set to 0, it becomes invalid.
Function Code Parameter Name Setting Range Default Unit Property
F9-01
Time for fan and lamp
to be turned off
0–240 2 min