The parameter setting in such wiring mode is described in the following table.
Table 5-6 Parameter setting under the shorting PMSM stator scheme
Function
Code
Parameter Name Value Description
F5-20 X20 function selection 7
Allocate X20 with the input "Shorting PMSM
stator feedback".
F7-03 Y3 function selection 05
Allocate Y3 with "Shorting PMSM stator
contactor".
FE-14
Elevator function
selection 2
-
Bit10 = 0: NC output contactor
Bit10 = 1: NO output contactor
More details on the emergency evacuation setting are provided in F6-69, as listed in the
following table.
Table 5-7 Parameter description of F6-69
Bit
Function
Description
Binary Setting Remarks
Bit0
Direction
determine
mode
0
Automatically
calculating
the direction
0
Load
direction
determining
(based on
load cell
data or half-
load signal)
1
Direction
of
nearest
landing
oor
If the torque
direction is
automatically
calculated, the no-
load-cell function
must be enabled,
that is, F8-01 is set
to 2.
Bit1 0 1 0
Bit2 Stop position
1 Stop at the base oor -
0 Stop at nearest landing oor -