Convert the binary value to decimal:
1 + 4 + 8 + 16 + 32 + 64 + 512 + 1024 + 4096 + 8192 + 16384 + 32768 = 63101
Then, enter "63101" for F6-05 on the operation panel.
Function Code Parameter Name Setting Range Default Unit Property
F6-06 Elevator function control 1 0–65535 0 -
★
It is used to select the required elevator functions.
Each bit of the function code denes a function, as described in the following table.
If a bit is set to 1, the function indicated by this bit is enabled; if this bit is set to 0, the
function is disabled.
Table 7-7 Functions indicated by bits of F6-06
F6-06 Elevator function control 1
Bit Function Description Default
Bit1
Returning to base oor
if position deviation too
large
The elevator stops at nearest landing oor and then
returns to the base oor for verication when the car
position deviation is too large.
0
Bit2 Reserved Reserved -
Bit3
Buzzer not tweet upon
re-leveling
The buzzer output relay does not work upon re-
leveling.
0
Bit5
Cancelling auto reset
of door lock fault
The door lock fault is not reset automatically. 0