Description of Function Codes NICE1000
new
User Manual
- 162 -
It is used to set the door open holding time after the elevator arrives at the base oor. The
elevator closes the door immediately after receiving a door close command.
Function Code Parameter Name Setting Range Default Unit Property
Fb-15 Arrival gong output delay 0–1000 0 ms
It is used to set the delay of arrival gong output.
Function Code Parameter Name Setting Range Default Unit Property
Fb-16
Door lock waiting time at
manual door
0–50 0 s
When the manual door function is enabled, the elevator responds to other calls only after
the time set in this parameter if the door lock is not disconnected upon arrival.
Function Code Parameter Name Setting Range Default Unit Property
Fb-17
Holding time for
forced door close
5–180 120 s
It is used to set the holding time before forced door close is implemented.
If the forced door close function is enabled, the system enters the forced door close state
and sends a forced door close signal when there is no door close signal after the time set in
this parameter is reached.
Group FC: Protection Function Parameters
Function Code Parameter Name Setting Range Default Unit Property
FC-00
Program control for
protection function
0–65535 0 -
It is used to set program control related to protection functions.
Each bit of the function code denes a function, as described in the following table.
If a bit is set to 1, the function indicated by this bit is enabled; if this bit is set to 0, the
function is disabled.
For details on how to view and set this function code in bit, refer to F6-06.
Table 7-17 Program control functions indicated by bits of FC-00
FC-00 Program control for protection function
Bit Function Description Default
Bit0
Short-circuit to
ground detection at
power-on
Whether the motor is short-circuited to ground is
detected at power-on. If the motor is short-circuited to
ground, the controller blocks the output immediately,
and reports the fault.
0
Bit1
Canceling current
detection at
inspection startup
You can cancel the limit on the maximum current at
startup for inspection.
0