Monarch NICE1000 - 5.2.1 Emergency Evacuation at Power Failure

Monarch NICE1000
205 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NICE1000
new
User Manual System Commissioning and Application Example
- 71 -
Figure 5-8 Various contacts of the contactors
X25
Safety contactor
53
54
11
14
Phase sequence relay
Safety
circuit
UPC
UPC
71 72
21
22
UPC
X19
24 V
Emergency
feedback
UPC
2
1
4
3
6
5 13
14 22
21
54
53
61
62
72
71
81
82
110 V
The UPS power is recommended in the following table.
Table 5-3 Recommended UPS power for each power class
UPS Power Controller Power
1 kVA (700–800 W) P ≤ 5.5 kW
2 kVA (1400–1600 W) 5.5 kW < P ≤ 11 kW
3 kVA (2100–2400 W) 15 kW ≤ P ≤ 22 kW
The following table lists the setting of the related parameters.
Table 5-4 Parameter setting under the 220 V UPS scheme
Function Code Parameter Name Setting
F6-72
Emergency evacuation switching
speed
0.010–0.630 m/s
F6-73 Evacuation parking oor 0 to F6-01
F8-09
Emergency evacuation operation
speed at power failure
0.000 to F3-11
F3-18
Emergency evacuation
acceleration rate
0.100–1.300 m/s
2
F8-10
Emergency evacuation operation
mode at power failure
0: Invalid
1: UPS
2: 48 V battery power supply
F5-19 (X19) X19 function selection 33 (UPS valid signal)
F7-00 (Y0) Y0 function selection
32 (Emergency evacuation
at power failure)