Cabinet Configuration and EMC Booksize
7.4 Arrangement of components and devices
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2
7-17
Two-tier configuration
Figure 7-5 Example of a two-tier configuration with modules between 200 and 300 mm wide
Continuation of the DC link with the DC link adapter (installation above) external to the
components is achieved using single-core, finely-stranded and shielded cables that are laid
so as to ensure they are short-circuit and ground-fault proof.
The distance between the two module rows depends on the wiring and cable cross-section.
For modules with a width of between 50 and 100 mm, the distance between the upper and
lower module row must be at least 300 mm.