D.3 UL Standards
Standards
Compliance
D
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual 453
Input Fuse Installation
The installation manual specifies that branch circuit protection should be provided by fuses listed in Table D.7.
Table D.7 Recommended Input Fuse Selection
4A0362
3/0 × 2P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080 100-051-558
4/0 × 2P
<1> 100-L12
TD-324,
TD-312
TP-100 100-051-560
250 × 2P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 2P
350 × 2P 180-L12
TD-327,
TD-314
TP-200
100-066-688
400 × 2P 200-L12 100-051-564
500
325-12
TD-328,
TD-315
TP-325 100-051-277
600
4A0414
4/0 × 2P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100 100-051-560
250 × 2P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 2P
<1>
4A0515
3/0 × 4P
<1> 3/0 × 4P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080 100-051-558
4/0 × 4P 4/0 × 4P
<1> 100-L12
TD-324,
TD-312
TP-100 100-051-560
250 × 4P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 2P
4A0675
4/0 × 4P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100 100-051-560
250 × 4P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 4P
<1>
4A0930
3/0 × 8P
M12
80-L12
YF-1
YET-300-1
TD-323,
TD-312
TP-080 100-051-558
4/0 × 8P
<1> 100-L12
TD-324,
TD-312
TP-100 100-051-560
250 × 8P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 8P
4A1200
4/0 × 8P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100 100-051-560
250 × 8P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 8P
<1>
<1> Recommended wire gauge
<2> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each
connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the
user should order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals,
so the user should order four sets of [100-051-560].
Model
CIMR-E
Fuse Type (Rated Voltage: 500 Vac)
Manufacturer: Bussmann
Model Fuse Ampere Rating (A)
Three-Phase 200 V Class
2A0004 FWH-70B 70
2A0006 FWH-70B 70
2A0008 FWH-70B 70
2A0010 FWH-70B 70
2A0012 FWH-70B 70
2A0018 FWH-90B 90
2A0021 FWH-90B 90
2A0030 FWH-100B 100
2A0040 FWH-200B 200
2A0056 FWH-200B 200
2A0069 FWH-200B 200
2A0081 FWH-300A 300
2A0110 FWH-300A 300
2A0138 FWH-350A 350
Model
CIMR-E
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp Terminal
Model Number
Tool
Insulation Cap
Model No.
Code <2>
R/L1, S/L2,
T/L3
U/T1, V/T2,
W/T3
Machine No. Die Jaw
SIEP_C710616_35.book 453 ペー 2015年11月30日 月曜日 午後2時2分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA E1000 and is the answer not in the manual?

YASKAWA E1000 Specifications

General IconGeneral
BrandYASKAWA
ModelE1000
CategoryController
LanguageEnglish