n
A2-33: User Parameter Automatic Selection
A2-33
determines whether or not parameters that have
been edited are saved to the User Parameters (A2-17 to A2-32) for
quick, easy access.
No. Parameter Name Setting Range Default
A2-33 User Parameter Automatic Selection 0 or 1
Depending on
A1-06
Setting 0: Do not save list of recently viewed parameters.
To manually select the parameters listed in the User Parameter group, set A2-33 to “0”.
Setting 1: Save history of recently viewed parameters.
By setting A2-33 to 1, all parameters that were recently edited will be automatically saved to A2-17 through A2-32. A
total of 16 parameters are saved in order with the most recently edited parameter set to A2-17. User parameters can be
accessed using the Setup mode of the digital operator.
5.1 A: Initialization
116
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual